Section 641.25.4. Amendments to Uniform Plumbing Code.  


Latest version.
  • The Uniform Plumbing Code (UPC), as adopted by reference in rule 641—25.1(105), shall be amended as follows:

             25.4(1) The following amendment shall apply to UPC Chapter 1:

    Subsection 101.11.5 Moved Buildings. Modify the subsection by deleting “except as provided for in Section 103.5.8.2” from the last sentence in the subsection.

             25.4(2) The following amendments shall apply to UPC Chapter 3:

                a.               Subsection 301.4.1 Permit Application. Delete the subsection.

                b.               Subsection 314.4.1 Installation of Thermoplastic Pipe and Fittings. Trench width for thermoplastic pipe shall be limited to six times the outside diameter of the piping at the base. Thermoplastic piping shall be bedded in not less than 4 inches (102 mm) of aggregate bedding material supporting the pipe. Initial backfill shall encompass the pipe. Aggregate material shall be three-eighths (3/8) inch p-gravel or 1-inch clean class one bedding.

             25.4(3) The following amendments shall apply to UPC Chapter 4:

                a.               Section 407.3 Limitation of Hot Water Temperature for Public Lavatories. Modify the section by adding the following sentence to the end of the section: “These devices shall be installed at or as close as possible to the point of use.”

                b.               Section 408.4 Waste Outlet. Modify the section by adding the following exception to the end of the section: “Exception: In a residential dwelling unit where a 2-inch waste pipe is not readily available and approval of the Authority Having Jurisdiction has been granted, the waste outlet, fixture tailpiece, trap and trap arm may be 1½ inch when an existing tub is being replaced by a shower sized per Section 408.6(2). This exception only applies where one shower head rated at 2.5 gpm is installed.”

                c.               Section 409.4 Limitation of Hot Water in Bathtubs and Whirlpool Bathtubs. Modify the section by adding the following sentence to the end of the section: “These devices shall be installed at or as close as possible to the point of use.”

                d.               Section 410.3 Limitation of Water Temperature in Bidets. Modify the section by adding the following sentence to the end of the section: “These devices shall be installed at or as close as possible to the point of use.”

                e.               Section 416.5 Drain. Modify the section by deleting the last sentence, which states: “Where a drain is provided, the discharge shall be in accordance with Section 811.0.”

                f.                Section 418.3 Location of Floor Drains. Modify the section by adding the following to the end of the section: “(5) Rooms equipped with a water heater.”

                g.               Subsection 421.1 General. Modify the subsection by deleting “Table 1401.1 of this code” and inserting the following in lieu thereof: “Chapter 11 of the 2015 International Building Code.”

                h.               Section 422.1 Fixture Count. Modify the section by deleting the first paragraph and inserting the following in lieu thereof: “Plumbing fixtures shall be provided in each building, for the type of building occupancy, and in the minimum number shown in Table 403.1 of the International Plumbing Code, reprinted here as Table 422.1. The design occupant load and occupancy classification shall be determined in accordance with Section 1004 of the 2015 International Building Code. Required public facilities shall be designated by a legible sign for each sex. Signs shall be readily visible and located near the entrance to each toilet facility.”

                i.                Subsection 422.1.1 Family or Assisted-Use Toilet and Bathing Facilities. Modify the subsection by adding the following sentence to the end of the subsection: “Required family or assisted-use fixtures are permitted to be included in the number of required fixtures for either the male or female occupants in assembly and mercantile occupancies.”

                j.                Table 422.1 Minimum Plumbing Facilities. Delete the table and insert the following table in lieu thereof:

    <fo:wrapper font-size="11pt">TABLE 422.1 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES<fo:wrapper font-size=".69em" baseline-shift=".33em">a</fo:wrapper></fo:wrapper>

    (Reprinted, with permission,* from the 2015 International Plumbing Code, excerpt from IPC Table 403.1)

    NO.

    CLASSIFICATION

    OCCUPANCY

    DESCRIPTION

    WATER CLOSETS (Urinals, see Sections 411.0 and 412.0)

    LAVATORIES

    BATHTUBS/

    SHOWERS

    DRINKING FOUNTAIN

    (See Section 415.0)

    OTHER

    MALE

    FEMALE

    MALE

    FEMALE

    1

    Assembly

    A-1d

    Theaters and other buildings for the performing arts and motion pictures

    1 per 125

    1 per 65

    1 per 200

    1 per 500

    1 service sink

    A-2d

    Nightclubs, bars, taverns, dance halls and buildings for similar purposes

    1 per 40

    1 per 40

    1 per 75

    1 per 500

    1 service sink

    Restaurants, banquet halls and food courts

    1 per 75

    1 per 75

    1 per 200

    1 per 500

    1 service sink

    A-3d

    Auditoriums without permanent seating, art galleries, exhibition halls, museums, lecture halls, libraries, arcades and gymnasiums

    1 per 125

    1 per 65

    1 per 200

    1 per 500

    1 service sink

    Passenger terminals and transportation facilities

    1 per 500

    1 per 500

    1 per 750

    1 per 1,000

    1 service sink

    Places of worship and other religious services

    1 per 150

    1 per 75

    1 per 200

    1 per 1,000

    1 service sink

    A-4

    Coliseums, arenas, skating rinks, pools and tennis courts for indoor sporting events and activities

    1 per 75 for the first 1,500 and 1 per 120 for the remainder exceeding 1,500

    1 per 40 for the first 1,520 and 1 per 60 for the remainder exceeding 1,520

    1 per 200

    1 per 150

    1 per 1,000

    1 service sink

    1

    Assembly (cont’d)

    A-5

    Stadiums, amusement parks, bleachers and grandstands for outdoor sporting events and activities

    1 per 75 for the first 1,500 and 1 per 120 for the remainder exceeding 1,500

    1 per 40 for the first 1,520 and 1 per 60 for the remainder exceeding 1,520

    1 per 200

    1 per 150

    1 per 1,000

    1 service sink

    2

    Business

    B

    Buildings for the transaction of business, professional services, other services involving merchandise, office buildings, banks, light industrial and similar uses

    1 per 25 for the first 50 and 1 per 50 for the remainder exceeding 50

    1 per 40 for the first 80 and 1 per 80 for the remainder exceeding 80

    1 per 100

    1 service sink<fo:wrapper font-size=".69em" baseline-shift=".33em">e</fo:wrapper>

    3

    Educational

    E

    Educational facilities

    1 per 50

    1 per 50

    1 per 100

    1 service sink

    4

    Factory and Industrial

    F-1 and F-2

    Structures in which occupants are engaged in work fabricating, assembly or processing of products or materials

    1 per 100

    1 per 100

    (See Section 416)

    1 per 400

    1 service sink

    5

    Institutional

    I-1

    Residential care

    1 per 10

    1 per 10

    1 per 8

    1 per 100

    1 service sink

    I-2

    Hospitals, ambulatory nursing home recipient

    1 per roomc

    1 per roomc

    1 per 15

    1 per 100

    1 service sink per floor

    Employees, other than residential careb

    1 per 25

    1 per 35

    1 per 100

    Visitors, other than residential care

    1 per 75

    1 per 100

    1 per 500

    5

    Institutional (cont’d)

    I-3

    Prisonsb

    1 per cell

    1 per cell

    1 per 15

    1 per 100

    1 service sink

    Reformatories, detention centers, and correctional centersb

    1 per 15

    1 per 15

    1 per 15

    1 per 100

    1 service sink

    Employeesb

    1 per 25

    1 per 35

    1 per 100

    I-4

    Adult day care and child care

    1 per 15

    1 per 15

    1

    1 per 100

    1 service sink

    6

    Mercantile

    M

    Retail stores, service stations, shops, salesrooms, markets and shopping centers

    1 per 500

    1 per 750

    1 per 1,000

    1 service sink<fo:wrapper font-size=".69em" baseline-shift=".33em">e</fo:wrapper>

    7

    Residential

    R-1

    Hotels, motels, boarding houses (transient)

    1 per sleeping unit

    1 per sleeping unit

    1 per sleeping unit

    1 service sink

    R-2

    Dormitories, fraternities, sororities and boarding houses (not transient)

    1 per 10

    1 per 10

    1 per 8

    1 per 100

    1 service sink

    R-2

    Apartment house

    1 per dwelling unit

    1 per dwelling unit

    1 per dwelling unit

    1 kitchen sink per dwelling unit; 1 automatic clothes washer connection per 20 dwelling units


    7

    Residential (cont’d)

    R-3

    Congregate living facilities with 16 or fewer persons

    1 per 10

    1 per 10

    1 per 8

    1 per 100

    1 service sink

    R-3

    One- and two-family dwellings and lodging houses with five or fewer guestrooms

    1 per dwelling unit

    1 per dwelling unit

    1 per dwelling unit

    1 kitchen sink per dwelling unit; 1 automatic clothes washer connection per dwelling unit

    R-4

    Congregate living facilities with 16 or fewer persons

    1 per 10

    1 per 10

    1 per 8

    1 per 100

    1 service sink

    8

    Storage

    S-1 and

    S-2

    Structures for the storage of goods, warehouses, storehouses and freight depots. Low and Moderate Hazard.

    1 per 100

    1 per 100

    See Section 416

    1 per 1,000

    1 service sink

    a    The fixtures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction of the number of persons indicated. The number of occupants shall be determined by the International Building Code.

    b    Toilet facilities for employees shall be separate from facilities for inmates or care recipients.

    c    A single-occupant toilet room with one water closet and one lavatory serving not more than two adjacent patient sleeping units shall be permitted provided that each patient sleeping unit has direct access to the toilet room and provision for privacy for the toilet room user is provided.

    d    The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of facilities required.

    e    For business and mercantile occupancies with an occupant load of 15 or fewer, service sinks shall not be required.

    *Excerpted (with modifications) from Table 403.1 of the 2015 International Plumbing Code; Copyright 2014; Washington, D.C.: International Code Council. Reproduced with permission. All rights reserved.  www.ICCSAFE.org

                k.               Insert the following text at the end of Chapter 4:

    “422.6 Pay Facilities. Where pay facilities are installed and permissible under Iowa law, such facilities shall be in excess of the required minimum facilities. Required facilities shall be free of charge.

    “422.7 Substitution for Water Closets. In each bathroom or toilet room, urinals shall not be substituted for more than 67 percent of the required water closets in assembly and educational occupancies. Urinals shall not be substituted for more than 50 percent of the required water closets in all other occupancies. (Reprinted from the 2015 International Plumbing Code section 419.2)”

             25.4(4) The following amendment shall apply to UPC Chapter 5:

    Sections 503.0 through 503.2 Inspection. Delete the sections.

             25.4(5) The following amendments shall apply to UPC Chapter 6:

                a.               Section 603.4.8 Drain Lines. Modify the section by adding the following language to the end of the section: “or in accordance with the manufacturer’s drain-sizing chart for installation.”

                b.               Section 609.11 Pipe Insulation. Delete sections 609.11 through 609.11.2 and insert the following in lieu thereof:

    Section 609.11 Pipe Insulation. Insulation of domestic hot water piping shall be in accordance with the applicable energy conservation code.

                c.               Section 611.4 Sizing of Residential Softeners. Modify the section by adding the following to the end of the last sentence in the section: “or as specified in the manufacturer’s installation instructions.”

                d.               Section 612 Residential Fire Sprinkler Systems. Delete sections 612.0 through 612.7.2.

             25.4(6) The following amendment shall apply to UPC Chapter 7:

    Section 710.1 Backflow Protection. Modify the section by adding the following sentences to the end of the section: “The requirement for the installation of a backwater valve shall apply only when determined necessary by the authority having jurisdiction based on local conditions. When a valve is required by the authority having jurisdiction, it shall be a manually operated gate valve or fullway ball valve. An automatic backwater valve may also be installed but is not required.”

             25.4(7) The following amendment shall apply to UPC Chapter 8:

    Section 804.7 Domestic Dishwashing Machine. Modify the section by deleting the section and inserting the following language in lieu thereof: “No domestic dishwashing machine shall be directly connected to a drainage system or food waste disposer without the use of an approved dishwasher air gap fitting on the discharge side of the dishwashing machine, or by looping the discharge line of the dishwasher as high as possible near the flood level of the kitchen sink where the waste disposer is connected. Listed air gap fittings shall be installed with the flood level (FL) marking at or above the flood level of the sink or drainboard, whichever is higher.”

             25.4(8) The following amendment shall apply to UPC Chapter 9:

                a.               Section 906.7 Frost or Snow Closure. Modify the section by deleting “two (2) inches (50.8 mm)” in the first sentence and inserting “three (3) inches (76.2 mm)” in lieu thereof.

                b.               Section 908.2.2 Size. Delete the second sentence in this section and insert the following new sentence in lieu thereof: “The wet vent shall be not less than 2 inches (50 mm) in diameter for 6 drainage fixture units (dfu) or less, and not less than 3 inches (80 mm) in diameter for 7 dfu or more.”

             25.4(9) The following amendment shall apply to UPC Chapter 10:

                a.               Table 1002.2 Horizontal Lengths of Trap Arms. Delete the table and insert the following table in lieu thereof:

    TABLE 1002.2

    Horizontal Lengths of Trap Arms

    (Except for Water Closets and Similar Features)<fo:wrapper font-size=".69em" baseline-shift=".33em">1,2</fo:wrapper>

     

    Trap Arm Diameter (inches)

    Distance Trap to Vent

    Minimum (inches)

    Length Maximum (feet)

     

    5

     

    3

    6

     

    2

    4

    8

     

    3

    6

    12

     

    4

    8

    12

     

    Exceeding 4

    2 × Diameter

    12

     

    <fo:wrapper font-size="8pt">For SI units: 1 inch = 25.4 mm</fo:wrapper>

    <fo:wrapper font-size="8pt">Notes:</fo:wrapper>

    <fo:wrapper font-size=".69em" baseline-shift=".33em">1</fo:wrapper><fo:wrapper font-size="8pt">Maintain ¼ inch per foot slope (20.8 mm/m).</fo:wrapper>

    <fo:wrapper font-size=".69em" baseline-shift=".33em">2</fo:wrapper><fo:wrapper font-size="8pt">The developed length between the trap of a water closet or similar fixture (measured from the top of the closet flange to the inner edge of the vent) and its vent shall not exceed 6 feet (1829 mm).</fo:wrapper>

                b.               Section 1014.1.3 Food Waste Disposers and Dishwashers. Modify the section by deleting the second sentence and inserting the following in lieu thereof: “Commercial food waste disposers shall discharge into the building’s drainage system in accordance with the requirements of the Authority Having Jurisdiction.”

             25.4(10) The following amendments shall apply to UPC Chapter 12:

                a.               Sections 1203.0 through 1203.4 Inspection. Delete the sections.

                b.               Sections 1204.0 through 1204.3 Certificate of Inspection. Delete the sections.

                c.               Sections 1205.0 through 1205.2 Authority to Render Gas Service. Delete the sections.

                d.               Sections 1207.0 and 1207.1 Temporary Use of Gas. Delete the sections.

             25.4(11) The following amendments shall apply to UPC Chapter 13:

                a.               Sections 1311.0 through 1311.4 Plan Review. Delete the sections.

                b.               Section 1326.3 Advance Notice. Delete the section.

                c.               Section 1326.4 Responsibility. Delete the section.

                d.               Section 1326.5 Testing. Delete the section.

                e.               Section 1326.6 Retesting. Modify the section by deleting “the Authority Having Jurisdiction finds that” and “or inspection” from the first sentence.

                f.                Section 1327.4 Report Items. Modify the section by deleting “Authority Having Jurisdiction” and inserting “responsible facility authority” in lieu thereof.

             25.4(12) The following amendment shall apply to UPC Chapter 15:

    Sections 1506.0 through 1506.4 Required Inspection. Delete the sections.

             25.4(13) The following amendments shall apply to UPC Chapter 16:

                a.               Section 1601.3 Permit. Delete the section.

                b.               Section 1601.6 Operation and Maintenance Manual. Modify the section by deleting “required to have a permit in accordance with Section 1601.3” from the first sentence.

                c.               Section 1603.2 Permit. Delete the section.

                d.               Subsection 1603.11.2.1 Visual System Inspection. Modify the subsection by deleting “by the Authority Having Jurisdiction and other authorities having jurisdiction” from the first sentence.

                e.               Subsection 1603.11.2.2 Cross-Connection Test. Modify the subsection by deleting “by the applicant in the presence of the Authority Having Jurisdiction and other authorities having jurisdiction” from the first sentence.

                f.                Subsection 1603.11.2.3 Discovery of Cross-Connection. Modify the subsection by deleting “in the presence of the Authority Having Jurisdiction.”

                g.               Section 1604.2 Plumbing Plan Submission. Delete the section.

                h.               Section 1604.5 Initial Cross-Connection Test. Modify the section by deleting “by the applicant in the presence of the Authority Having Jurisdiction and other authorities having jurisdiction,” and by deleting the final sentence (“The test shall be ruled successful by the Authority Having Jurisdiction before final approval is granted.”).

                i.                Subsection 1604.12.2.1 Visual System Inspection. Modify the subsection by deleting “by the Authority Having Jurisdiction and other authorities having jurisdiction.”

                j.                Subsection 1604.12.2.2 Cross-Connection Test. Modify the subsection by deleting “in the presence of the Authority Having Jurisdiction and other authorities having jurisdiction.”

                k.               Subsection 1604.12.2.3 Discovery of Cross-Connection. Modify the subsection by deleting “in the presence of the Authority Having Jurisdiction.”

             25.4(14) The following amendments shall apply to UPC Chapter 17:

                a.               Section 1702.2 Plumbing Plan Submission. Delete the section.

                b.               Section 1702.5 Initial Cross-Connection Test. Modify the section by deleting the second and third sentences (“Before the building is occupied or the system is activated, the installer shall perform the initial cross-connection test in the presence of the Authority Having Jurisdiction and other authorities having jurisdiction. The test shall be ruled successful by the Authority Having Jurisdiction before final approval is granted.”).

                c.               Subsection 1702.11.2.1 Visual System Inspection. Modify the subsection by deleting “by the Authority Having Jurisdiction and other authorities having jurisdiction.”

                d.               Subsection 1702.11.2.2 Cross-Connection Test. Modify the subsection by deleting “by the applicant in the presence of the Authority Having Jurisdiction and other authorities having jurisdiction.”

                e.               Subsection 1702.11.2.3 Discovery of Cross-Connection. Modify the subsection by deleting “in the presence of the Authority Having Jurisdiction.”

    [ARC 8860B, IAB 6/16/10, effective 7/21/10; ARC 1089C, IAB 10/16/13, effective 11/20/13; ARC 2474C, IAB 3/30/16, effective 6/1/16]